Choose the box and count what goes in it, and Busbar adds up the volume NEC 314.16 requires: each conductor, loops counted twice, two allowances per device yoke, one for clamps and one for the grounds plus a quarter for each beyond four. It has every standard metal box from Table 314.16(A) and takes the marked volume of plastic boxes, extension rings and raised covers. It is free with no sign-up; Pro is US$9 a month for a PDF report. Devices and clamps are counted at the largest conductor in the box, which is never less than the code requires.

  • All standard metal boxes
  • Plastic boxes by marked volume
  • No sign-up
Box fill calculator
Box
Conductors entering the box (not grounds)
Unbroken loops long enough to count twice
Devices, clamps and grounds

Switches and receptacles

Fits: 22.50 in³ needed, 30.3 in³ available

NEC 314.16 · 4 × 2-1/8 square metal box

Volume required

6 × 12 AWG conductors (6 × allowance)
13.50 in³
Internal cable clamps (one allowance, 12 AWG) (1 × allowance)
2.25 in³
1 device yoke(s), two 12 AWG allowances each (2 × allowance)
4.50 in³
3 equipment grounding conductor(s), one allowance (1 × allowance)
2.25 in³
Total required
22.50 in³

Box

4 × 2-1/8 square metal box
30.3 in³
  • Clamp, support-fitting, device and grounding allowances are taken at the largest conductor in the box, which is the same as or more than 314.16(B) requires.
  • Conductors that do not leave the box, such as pigtails, are not counted; up to four fixture wires smaller than 14 AWG from a luminaire canopy may be omitted (314.16(B)(1) Exception).

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the box

    A standard metal box from the table, or the cubic inches marked inside a plastic box.

  2. 02

    Count the conductors

    Conductors entering by size, unbroken loops, device yokes, clamps, fixture studs and grounds.

  3. 03

    Compare the volume

    Required cubic inches against the box, with each allowance and its 314.16(B) rule.

Questions

How many 12 AWG wires fit in a 4 × 1-1/2 square box?

Nine, with nothing else in the box: 21.0 in³ ÷ 2.25 in³ per 12 AWG conductor. Every device, clamp and the grounds take more of that volume.

Do pigtails count?

No. A conductor that starts and ends inside the box, such as a pigtail, is not counted. Up to four fixture wires smaller than 14 AWG from a luminaire canopy can be left out too.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.