Conduit fill calculator

Pick the conduit type and size and list the conductors, grounds included, and Busbar adds up their areas from NEC Chapter 9 and checks them against the 53, 31 or 40 % limit, or 60 % for a short nipple. It covers EMT, PVC Schedule 40 and 80, RMC, IMC, FMC, LFMC and ENT with THHN/THWN-2, XHHW-2, THW/TW and bare conductors, and finds the smallest size that fits. It is free with no sign-up; Pro is US$9 a month for a PDF report. Cables and compact conductors are not in the tables yet.

  • Eight raceway types
  • Smallest size that fits
  • No sign-up
Conduit fill calculator
Raceway

A short raceway between boxes may be filled to 60 %.

Conductors, including grounds

Fits: 17.5 % of 40 % allowed

NEC Chapter 9, Tables 1, 4, 5 and 8 · EMT 1/2 in

Conductors

3 × 12 AWG THHN/THWN-2
0.0399 in²
1 × 12 AWG THHN/THWN-2
0.0133 in²
Total, 4 conductors
0.0532 in²

Raceway

EMT 1/2 in, total area
0.304 in²
Allowed fill for over two conductors
40 %
Allowed area
0.1216 in²
Fill
17.5 %
Smallest EMT that fits
1/2 in
  • Equipment grounding and bonding conductors are counted (Chapter 9, Table 1, Note 3).
  • Check the raceway article for any lower conductor count, and adjust conductor ampacity for more than three current-carrying conductors per 310.15(C)(1).

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the raceway

    Conduit or tubing type and trade size; mark it as a nipple if it is 24 in or shorter.

  2. 02

    List the conductors

    Count, size and insulation for each group, equipment grounding conductors included.

  3. 03

    Read the fill

    Total area, fill percent against the allowed limit, and the smallest size of the same raceway that fits.

Questions

Do ground wires count in conduit fill?

Yes. Equipment grounding and bonding conductors count toward fill (Chapter 9, Table 1, Note 3). Bare conductors use their area from Table 8.

Why is the limit 31 % for two wires?

Two round conductors can jam against each other when pulled, so Chapter 9 Table 1 allows less for two than for one (53 %) or three and more (40 %).

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.