Pick the system, conductor and size, then enter the one-way length and current, and Busbar gives the drop in volts and percent from the NEC Chapter 9 Table 8 resistance, plus the smallest size that stays within your target. It handles copper and aluminum, 120 to 480 V single- and three-phase, DC and parallel sets. It is free with no sign-up; Pro is US$9 a month for a schedule of up to 50 circuits in one PDF report. It uses DC resistance at 75 °C, so very large AC feeders can differ slightly from an impedance-based result.

  • Copper and aluminum
  • Smallest size within target
  • No sign-up
Voltage drop calculator
Circuit
ft
A
%

3 % for a branch circuit, 5 % feeder plus branch

5.28 % drop (6.34 V) — over 3 %

8 AWG keeps the drop within 3 %.

NEC Chapter 9, Table 8 resistance at 75 °C · single-phase and DC × 2, three-phase × 1.732

Circuit

System
120 V single-phase
Conductor
12 AWG copper
Resistance
1.98 ohm/kft
One-way length
100 ft
Load current
16.0 A
Voltage drop
6.34 V
Voltage drop
5.28 %
Voltage at the load
113.7 V
Smallest copper size within 3 %
8 AWG
Ampacity at 75 °C; overcurrent device limited to 20 A
25 A
  • The NEC recommends, in informational notes to 210.19 and 215.2, no more than 3 % drop on a branch circuit and 5 % on the feeder and branch circuit together; these are not mandatory unless adopted locally.
  • DC resistance from Table 8 ignores reactance; for large conductors on AC, Table 9 effective impedance gives a slightly different result.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the circuit

    Voltage and phase, copper or aluminum, and the conductor size you plan to use.

  2. 02

    Enter length and load

    One-way length in feet and the load current in amps; add parallel sets for large feeders.

  3. 03

    Check against 3 %

    See the drop and the voltage at the load, and the smallest size that keeps it within your target.

Questions

Does the NEC require 3 % voltage drop?

Not in the main code. Informational notes to 210.19 and 215.2 recommend no more than 3 % on a branch circuit and 5 % on the feeder and branch circuit together. Some codes, such as energy codes, and some jurisdictions make it mandatory.

Which formula does it use?

Drop = 2 × length × resistance × current ÷ 1,000 for single-phase and DC, and 1.732 × length × resistance × current ÷ 1,000 for three-phase, with resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation